Technical Specifications of Busbar Ducts:
- 1.Rating : Upto 6300A
- 2.Application : Indoor and Outdoor as per customer requirements
- 3.Standard : IEC61439-1 and 2/3
- 4.Structure Type : Fixed with bolted covers
- 5.Paint Finishing : Electrostatic Powder Coating
- 6.Mounting : On Walls and or Ceilings
- 7.System Voltage : 230/415V, 50Hz, AC
- 8.Insulation Voltage : 1000 V
- 9.Short Circuit withstand Capacity Ranges : 50KA, 65KA and 100KA
- 10.Degree of Ingress Protection against solids and liquids : Upto IP-65
- 11.Ambient Temperature : 40 Degree Centigrade
- 12.Degree of Pollution : 1
- 13.Type of Earthing System : TN-S
- 14.Type of Conductor : Copper or Aluminum